1 a: initialization, A1: initialization, A1-00: language selection – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 150: A1-01: access level selection

150
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
5.1 A: Initialization
5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
◆ A1: Initialization
■
A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
Setting 8: Czech
Setting 9: Russian
Setting 10: Turkish
Setting 11: Polish
Setting 12: Greek
■
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
Setting 0: Operation only
Access is restricted to parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all
A2 parameters cannot be modified.
• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
digital operator until an Enter command is issued to the drive from the serial communication.
No.
<1> Language Settings 8 to 12 can only be selected from an LCD operator with software version 0102 or later. The version number of the LCD
operator PRG software is shown on the back of the LCD operator.
Parameter Name
Setting Range
Default
A1-00
Language Selection
0 to 12
0
No.
Parameter Name
Setting Range
Default
A1-01
Access Level Selection
0 to 2
2