E5-06: motor d-axis inductance, E5-07: motor q-axis inductance, E5-09: motor induction voltage constant 1 – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 185: E5-11: encoder offset, E5-24: motor induction voltage constant 2, 5 e: motor parameters

5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
185
P
a
ra
me
te
r De
ta
ils
5
■
E5-06: Motor d-Axis Inductance
Sets the d-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
■
E5-07: Motor q-Axis Inductance
Sets the q-Axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.
■
E5-09: Motor Induction Voltage Constant 1
Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. This data can be obtained from either
the motor nameplate or from the motor test report issued by the manufacturer of the motor.
Note: 1. Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger OPE08. OPE08 will also be triggered if
neither E5-09 nor E5-24 are set to 0.0.
2. This parameter is not reset when the drive is initialized using parameter A1-03.
■
E5-11: Encoder Offset
Sets the offset between the rotor magnetic axis and the Z-pulse of the encoder connected. This parameter is set during
Auto-Tuning for PM motors and during Encoder Offset Tuning.
■
E5-24: Motor Induction Voltage Constant 2
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. This data can be obtained
from either the motor nameplate or from the motor test report issued by the manufacturer of the motor.
Note: 1. Set E5-09 to 0.0 when setting E5-24. However, setting both E5-09 and E5-24 to 0.0 will trigger OPE08. OPE08 will also be triggered
if neither E5-09 nor E5-24 are set to 0.0.
2. This parameter is not reset when the drive is initialized using parameter A1-03.
No.
Parameter Name
Setting Range
Default
E5-06
Motor d-Axis Inductance
0.00 to 600.00 mH
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E5-07
Motor q-Axis Inductance
0.00 to 600.00 mH
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E5-09
Motor Induction Voltage Constant 1
0.0 to 6500.0 mV/(rad/s)
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E5-11
Encoder Offset
-180.0 to 180.0 deg
0.0 deg
No.
Parameter Name
Setting Range
Default
E5-24
Motor Induction Voltage Constant 2
0.0 to 6500.0 mV/(r/min)
0.0 mv/(r/min)