B.3 Parameter Table
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
383
Pa
ra
met
er
L
is
t
B
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
15
Fast Stop (N.O.)
Closed: Decelerates to stop at the Fast Stop ramp set to C1-09.
16
Motor 2 Selection
Open: Motor 1(E1-, E3-)
Closed: Motor 2 (E2-, E4-)
17
Fast Stop (N.C.)
Open: Decelerates to stop at the Fast Stop ramp set to C1-09.
18
Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2- = 12).
1A
Accel/decel Ramp Selection 2
Used in conjunction with an input terminal set for “Accel/decel ramp selection 1” (H1- = 7), and allows the
drive to switch between accel/decel ramp 3 and 4.
20 to 2F
External Fault
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
50
Nominal Speed
Closed: Activates the nominal speed (d1-19).
51
Intermediate Speed
Closed: Activates the Intermediate Speed (d1-20).
52
Releveling Speed
Closed: Activates the Releveling Speed (d1-23).
53
Leveling Speed
Closed: Activates the Leveling Speed (d1-26).
54
Inspection Operation
Closed: Activates Inspection operation using the speed set in d1-24.
55
Rescue Operation
Closed: Activates rescue operation.
56
Motor Contactor Feedback
Used for motor contactor supervision and fault detection.
57
High Speed Limit (Up)
Closed: Uses the leveling speed as the maximum speed when going up.
58
High Speed Limit (Down)
Closed: Uses the leveling speed as the maximum speed when going down.
5A
Motor Contactor Feedback 2
Open: Motor contactor closed (N.C.)
Closed: Motor contactor open
5B
Brake Feedback 2
Open: Brake open (N.C.)
Closed: Brake closed
H1 Multi-Function Digital Input Settings
H1-
Setting
Function
Description
Page
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_