E4: motor 2 parameters, E4-01: motor 2 rated current, E4-02: motor 2 rated slip – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 183: E4-03: motor 2 rated no-load current, E4-04: motor 2 motor poles, 5 e: motor parameters

5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
183
P
a
ra
me
te
r De
ta
ils
5
◆ E4: Motor 2 Parameters
E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the Auto-Tuning
process for vector control modes (Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2).
if Auto-Tuning cannot be performed.
Note: The function for switching between two motors cannot be used with a PM motor. E4- parameters are hidden when a PM
motor control mode is selected (A1-02 = 7).
■
E4-01: Motor 2 Rated Current
Protects the motor and calculates torque limits. Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor
2.
If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E4-01.
Note: 1. The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display
values in 0.01 A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.
2. An oPE02 error will occur if the motor rated current in E4-01 is set lower than the motor no-load current in E4-03. Set E4-03 correctly
to prevent this error.
■
E4-02: Motor 2 Rated Slip
Sets the motor 2 rated slip frequency and is the basis for slip compensation value. The drive calculates this value
automatically during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
for information on calculating the motor rated slip.
■
E4-03: Motor 2 Rated No-Load Current
Sets the no-load current for motor 2 in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-
load current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer for a
copy of the motor test report.
Note: The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display
values in 0.01 A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.
■
E4-04: Motor 2 Motor Poles
Sets the number of poles for motor 2. If Auto-Tuning completes successfully, the value entered to T1-06 will be
automatically saved to E4-04.
No.
Parameter Name
Setting Range
Default
E4-01
Motor 2 Rated Current
10 to 200% of the drive rated current.
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E4-02
Motor 2 Rated Slip
0.00 to 20.00 Hz
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E4-03
Motor 2 Rated No-Load Current
0 to [E4-01]
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E4-04
Motor 2 Motor Poles
2 to 48
4