B.3 Parameter Table
374
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
◆ d: Speed References
Speed Reference parameters are used to set the various speed reference values during operation.
■
d1: Speed Reference
C6-31
(77AH)
Carrier Frequency during Rescue
Operation
Sets the carrier frequency during Rescue Operation.
0: C6-03 setting
1: 2 kHz
Default: 0
Min: 0
Max: 1
<4> Default setting value varies by the drive model (o2-04).
No.(Addr.)
Name
Description
Setting
Page
d1-01
(280H)
Speed Reference 1
Sets the Speed reference for the drive when d1-18 is set to 0 or 3. Setting units are determined
by parameter o1-03.
Default: 0.00%
Min: 0.00%
Max: 100.00%
d1-02
(281H)
Speed Reference 2
d1-03
(282H)
Speed Reference 3
d1-04
(283H)
Speed Reference 4
d1-05
(284H)
Speed Reference 5
d1-06
(285H)
Speed Reference 6
d1-07
(286H)
Speed Reference 7
d1-08
(287H)
Speed Reference 8
d1-18
(2C0H)
Speed Reference Selection Mode
Sets the mode of speed reference selection by digital inputs.
0: Use multi-speed references (d1-01 to d1-08)
1: High speed reference has priority (d1-19 to d1-23, d1-26)
2: Leveling speed reference has priority (d1-19 to d1-23, d1-26)
3: Use multi-speed references d1-02 to d1-08, no speed selection stops the drive. Drive will stop
when all input terminals programmed for speed references (H1-
= 3, 4, 5) are open.
Default: 0
Min: 0
Max: 3
d1-19
(2C1H)
Nominal Speed
Sets the nominal speed reference when d1-18 = 1 or 2.
Default: 100.00%
Min: 0.00%
Max: 100.00%
d1-20
(2C2H)
Intermediate Speed 1
Sets intermediate speed reference 1 when d1-18 = 1 or 2.
Default: 0.00%
Min: 0.00%
Max: 100.00%
d1-21
(2C3H)
Intermediate Speed 2
Sets intermediate speed reference 2 when d1-18 = 1 or 2.
Default: 0.00%
Min: 0.00%
Max: 100.00%
d1-22
(2C4H)
Intermediate Speed 3
Sets intermediate speed reference 3 when d1-18 = 1 or 3.
Default: 0.00%
Min: 0.00%
Max: 100.00%
No.(Addr.)
Name
Description
Setting
Page
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_