B.3 Parameter Table
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
401
Pa
ra
met
er
L
is
t
B
■
S5: Short Floor Operation
■
S6: Error Detection
No. (Addr.)
Name
Description
Setting
Page
S5-01
(6ABH)
<36> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 650.00 inches.
<37> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 393.00 inches.
Short Floor Operation Selection
0: Disabled
1: Enabled (Short Floor)
2: Enabled (Advance Short Floor)
Default: 0
Min: 0
Max: 2
S5-02
(6ACH)
Nominal Speed for Short Floor
Calculation
When d1-18 (Speed Priority Selection) is set to 0 or 3, S5-02 determines the rated speed used
during Short Floor.
Default: 0.0%
Min: 0.0%
Max: 100.0%
S5-03
(6ADH)
Short Floor Minimum Constant
Speed Time
Sets the minimum operation time when the Advanced Short Floor function is enabled (S5-01 =
2).
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
S5-04
(6AEH)
Distance Calculation Acceleration
Time Gain
Set for acceleration jerk compensation in Distance Calculation.
Default: 150.0%
Min: 50.0%
Max: 200.0%
S5-05
(6AFH)
Distance Calculation Deceleration
Time Gain
Set for deceleration jerk compensation in Distance Calculation.
Default: 150.0%
Min: 50.0%
Max: 200.0%
S5-10
(6B0H)
Stopping Method Selection
0: Disabled
1: Direct Landing
2: Leveling Distance Control
Default: 0
Min: 0
Max: 2
S5-11
(6B1H)
Deceleration Distance
Sets the deceleration distance when Stop Distance Control is enabled.
Default: 0 mm
Min: 0 mm
Max: 32767 mm
S5-12
(6B2H)
Stop Distance
Sets the stopping distance when Stop Distance Control is enabled.
Default: 0 mm
Min: 0 mm
Max: 10000 mm
S5-13
(6D6H)
Direct Landing Minimum Speed
Level
Sets the speed level for the start of Direct Landing.
Direct Landing is essentially disabled if the starting speed for Direct Landing is less than the
maximum output speed multiplied by this parameter (E1-04
× S5-13).
Default: 20%
Min: 0%
Max: 100%
No. (Addr.)
Name
Description
Setting
Page
S6-01
(6B3H)
Motor Contactor Response Error
(SE1) Detection/Reset Selection
0: Detect during stop, SE1 must be manually reset
1: Detect during stop, SE1 can be automatically reset
2: No SE1 detection
Default: 0
Min: 0
Max: 2
S6-02
(6B4H)
Starting Current Error (SE2)
Detection Delay Time
Sets a delay time for detecting SE2.
Default: 200 ms
Min: 0.00 ms
Max: [S1-04]-[S1-06]
S6-03
(6B5H)
SE2 Detect Current Level
Sets the level of current applied to the motor when the Brake Control command is activated, as
a percentage of the Motor No-load Current (E2-03).
Default: 25%
Min: 0%
Max: 100%
S6-04
(6B6H)
Output Current Error (SE3)
Detection Delay Time
Sets a delay time for detecting SE3.
Default: 200 ms
Min: 0 ms
Max: 5000 ms
S6-05
(6B7H)
Brake Response Error (SE4)
Detection Time
Sets a delay time for detecting SE4.
Default: 500 ms
Min: 0 ms
Max: 10000 ms
S6-10
(6B8H)
Overacceleration Detection Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overspeed fault (dv6)
and has the motor coast to stop. Parameter S6-10 determines the acceleration rate that triggers a
fault.
Default:
Min: 0.0 m/s
2
Max: 20.0 m/s
S6-11
(6B9H)
Overacceleration Detection Time
Sets a primary delay for detecting overacceleration.
Default: 50 ms
Min: 0 ms
Max: 5000 ms
S6-12
(6BAH)
Overacceleration Detection
Selection
0: Always enabled
1: During run only
Default: 0
Min: 0
Max: 1
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
common
_
All Modes
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
All Modes
common
_
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV