◆ C6: Carrier Frequency
■
C6-03: Carrier Frequency
Sets the carrier frequency.
■
C6-06: PWM Method
Determines how the drive should perform pulse width modulation.
Setting 0: 2-phase/3-phase conversion
Setting 1: 2-phase modulation
Setting 2: 3-phase modulation
Note: The drive rated output current is reduced with setting 2. Contact Yaskawa or a Yaskawa representative for details.
■
C6-09: Carrier Frequency during Rotational Auto-Tuning
Determines the carrier frequency while performing Rotational Auto-Tuning. Although this parameter rarely needs to be
changed, when overcurrent problems occur when Auto-Tuning a low impedance motor, it may be helpful to set C6-03 to
a high value before setting C6-09 to 1.
Setting 0: 5 kHz
Setting 1: Same value set to C6-03
■
C6-21: Inspection Operation Carrier Frequency
Sets the carrier frequency during Inspection Run.
Setting 0: Use the value set to C6-03
Setting 1: 2 kHz
■
C6-23: Carrier Frequency during Initial Motor Pole Search
Sets the carrier frequency when estimating the initial polarity.
Setting 0: 2 kHz
Setting 1: Use the value set to C6-03
No.
Parameter Name
Setting Range
Default
C6-03
Carrier Frequency
1.0 to 15.0 kHz
Determined by o2-04
No.
Parameter Name
Setting Range
Default
C6-06
PWM Method
0 to 2
0
No.
Parameter Name
Setting Range
Default
C6-09
Carrier Frequency during Rotational Auto-Tuning
0 or 1
0
No.
Parameter Name
Setting Range
Default
C6-21
Inspection Operation Carrier Frequency
0 or 1
1
No.
Parameter Name
Setting Range
Default
C6-23
Carrier Frequency during Initial Motor Pole Search
0 or 1
0