◆ b2: Magnetic Flux Compensation
■
b2-08: Magnetic Flux Compensation Value
Sets the magnetic flux compensation at start as a percentage of the no-load current value (E2-03). This function allows for
the development of more flux to facilitate starting machines that require high starting torque or motors with a large rotor
time constant.
When an Up/Down command is issued, the DC current level injected into the motor changes linearly from the level set to
b2-08 to the level set to E2-03 within the time set to b2-03.
Figure 5.1
Figure 5.1 Magnetic Flux Compensation
The level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor rated current,
whichever value is smaller.
Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to S1-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.
◆ b4: Delay Timers
The timer function is independent of drive operation and can delay the switching of a digital output triggered by a digital
input signal and help eliminate chattering switch noise from sensors. An on-delay and off-delay can be set separately.
To enable the timer function, set a multi-function input to Timer input (H1-=18) and set a multi-function output to
Timer output (H2-=12). Only one timer can be used.
■
b4-01, b4-02: Timer Function On-Delay, Off-Delay Time
b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.
No.
Parameter Name
Setting Range
Default
b2-08
Magnetic Flux Compensation Value
0 to 1000%
0%
No.
Parameter Name
Setting Range
Default
b4-01
Timer Function On-Delay Time
0.0 to 3000.0 s
0.0 s
b4-02
Timer Function Off-Delay Time
0.0 to 3000.0 s
0.0 s
E2-03
Time
S1-04
Magnetizing Current
Reference
b2-08
Output Speed
common_TMo