S3-14: torque compensation fade out speed, S3-15: torque compensation fade out time, S3-16: torque limit reduction time – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 252: S3-20: dwell 2 speed reference, 11 s: elevator parameters, Sets the speed reference for the dwell 2 function

5.11 S: Elevator Parameters
252
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
■
S3-12: Starting Torque Compensation Bias in Down Direction
Adds a bias to torque compensation in Down direction.
Refer to Adjusting the Torque Compensation at Start on page 127
for details.
■
S3-14: Torque Compensation Fade Out Speed
Sets the speed level for torque compensation to fade out during the time determined by S3-15. Set as a percentage of the
maximum output frequency (E1-04). A setting of 0.0% disables this function.
■
S3-15: Torque Compensation Fade Out Time
Sets the time for torque compensation to fade out when motor speed reaches the level set in S3-14.
■
S3-16: Torque Limit Reduction Time
After Position Lock at stop, S3-16 determines the length of time to reduce the torque limit rate =
■
S3-20: Dwell 2 Speed Reference
Sets the speed reference for the Dwell 2 function.
Note: Setting this parameter to 0.00 disables the Dwell 2 function.
Figure 5.47
Figure 5.47 Dwell Speed Reference at Start
No.
Parameter Name
Setting Range
Default
S3-12
Starting Torque Compensation Bias in Down Direction
–40.0 to 40.0%
0.00%
No.
Parameter Name
Setting Range
Default
S3-14
Torque Compensation Fade Out Speed
0.0 to 100.0%
0.0%
No.
Parameter Name
Setting Range
Default
S3-15
Torque Compensation Fade Out Time
0 to 5000 ms
1000 ms
No.
Parameter Name
Setting Range
Default
S3-16
Torque Limit Reduction Time
0 to 10000 ms
100 ms
No.
Parameter Name
Setting Range
Default
S3-20
Dwell 2 Speed Reference
0.00 to 100.00
0.00%
Torque 300%
S3-16
Run Command
C1-07
C2-01
S3-21
C1-01
ON
SFS output
Motor speed
S3-20