Connecting an ac reactor or a dc link choke, Placement, Connecting an ac reactor – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 351: Yea_t monly, 5 installing peripheral devices

8.5 Installing Peripheral Devices
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
351
Per
iphe
ra
l De
vi
ce
s &
Optio
n
s
8
◆ Connecting an AC Reactor or a DC Link Choke
■
Placement
When connecting to a power supply transformer with greater than 600 kVA capacity, or when switching a phase advance
capacitor, large peak current can flow through the input power supply circuit and damage converter components in the
drive.
As a preventive measure, install an AC reactor or a DC link choke to the input side of the drive. Installing an AC reactor
or a DC link choke will also help improve the power factor.
Install an AC reactor or a DC link choke if a DC drive or another type of thyristor converter is running from the same
power system, regardless of the power supply conditions shown in
Note: A DC link choke is built in to the drive models 2A0106 to 2A0432 and 4A0056 to 4A0260.
Figure 8.17
Figure 8.19 Installing an AC Reactor or DC Link Choke
■
Connecting an AC Reactor
Figure 8.18
Figure 8.20 Connecting an AC Reactor
A – Power supply
C – AC reactor
B – MCCB
D – Drive
4000
600
0
60
400
Drive Capacity (kVA)
Power Supply
Capacity (kVA)
Power supply harmonics
AC reactor or DC link choke
required
AC reactor or DC link
choke unnecessary
YEA_T
Monly
B
A
C
D
R/L1
U
V
W
X
Y
Z
S/L2
T/L3
C o m m
on_
TMonly