5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
193
P
a
ra
me
te
r De
ta
ils
5
5.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
◆ H1: Multi-Function Digital Inputs
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-
01 (Speed Reference Selection), or H1-
(Multi-Function Digital Inputs). If the RUN command is on when changing any of these
settings, the motor may unexpectedly start running, and could result in injury.
■
H1-03 to H1-08: Functions for Terminals S3 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and their settings are listed
in
Table 5.9 Multi-Function Digital Input Terminal Settings
Setting 3 to 5: Multi-Step Speed Reference 1 to 3
Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs.
Refer to Speed Selection Using Digital
Inputs (b1-01 = 0) on page 121
for details.
Setting 6: Jog reference selection
When the speed reference is not assigned to the input terminals (b1-01
≠ 1), then the Jog frequency will be activated every
time an input terminal set for the Jog frequency reference closes. Note that the speed reference priority selection in d1-18
may disable the Jog frequency.
Table 5.10 Speed Reference Priority and Jog Frequency
No.
<1> With the speed reference priority d1-18 is set to 0 or 3, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7
are: 24, 14, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F
respectively.
Parameter Name
Setting
Range
Default
H1-03
Terminal S3 Function Selection
3 to 79
Determined by d1-18
H1-04
Terminal S4 Function Selection
3 to 79
H1-05
Terminal S5 Function Selection
3 to 79
H1-06
Terminal S6 Function Selection
3 to 79
H1-07
Terminal S7 Function Selection
3 to 79
H1-08
Terminal S8 Function Selection
3 to 79
F: Through Mode
Setting
Function
Page
Setting
Function
Page
3
Multi-Step Speed Reference 1
20 to 2F
External Fault
4
Multi-Step Speed Reference 2
50
Nominal Speed
5
Multi-Step Speed Reference 3
51
Intermediate Speed
6
Jog reference selection
52
Releveling Speed
7
Accel/decel Ramp Selection 1
53
Leveling Speed
8
Baseblock Command (N.O.)
54
Inspection Operation
9
Baseblock Command (N.C.)
55
Rescue Operation
F
Not used (Through Mode)
56
Motor Contactor Feedback
14
Fault Reset
57
High Speed Limit Up
15
Fast Stop (N.O.)
58
High Speed Limit Down
16
Motor 2 selection
5A
Motor Contactor Feedback 2
17
Fast Stop (N.C.)
5B
Brake Feedback 2
18
Timer Function Input
5C
Stop Distance Correction
1A
Accel/decel Ramp Selection 2
67
Communications Test Mode
79
Brake Feedback
d1-18 (Speed Reference
Selection Mode)
Jog Frequency
0
Multi-speed references take priority, and the leveling speed in d1-26 is used for the Jog frequency.
1
Jog frequency cannot be used.
2
Jog frequency cannot be used.