H5-05: communication fault detection selection, H5-06: drive transmit wait time, H5-07: rts control selection – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 423: H5-09: communication fault detection time, Common_ tmonly, Enables or disables rts control

C.4 MEMOBUS/Modbus Setup Parameters
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
423
MEMOBUS
/Mo
dbu
s
C
o
m
m
u
ni
ca
ti
on
s
C
■
H5-05: Communication Fault Detection Selection
Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus communications.
Setting 0: Disabled
No communication error detection. The drive continues operation.
Setting 1: Enabled
If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered
and the drive will operate as determined by parameter H5-04.
■
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master before responding.
Figure C.6
Figure C.6 Drive Transmit Wait Time Setting
■
H5-07: RTS Control Selection
Enables or disables RTS control.
Setting 0: Disabled. RTS is always on.
Use this setting when using RS-485 signals for communications or when using RS-422 signals for point-to-point
communications.
Setting 1: Enabled. RTS switches while sending.
Use this setting when using RS-422 signals for multi-drop communications.
■
H5-09: Communication Fault Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault.
No.
Parameter Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
No.
Parameter Name
Setting Range
Default
H5-06
Drive Transmit Wait Time
5 to 65 ms
5 ms
No.
Parameter Name
Setting Range
Default
H5-07
RTS Control Selection
0 or 1
1
No.
Parameter Name
Setting Range
Default
H5-09
Communication Fault Detection Time
0.0 to 10.0 s
2.0 s
Command message
Response message
Command message
PLC→Drive
PLC→Drive
Drive→PLC
Time
24 bit length
H5-06 setting
common_
TMonly