L4: Speed Detection
■
L5: Automatic Fault Reset
■
L6: Torque Detection
<16> The setting value is dependent on the setting for the carrier frequency reduction (L8-38).
No. (Addr.)
Name
Description
Setting
Page
L4-01
(499H)
Speed Agreement Detection Level
L4-01 sets the speed detection level for digital output functions H2- = 3, 4, 5.
L4-02 sets the hysteresis or allowable margin for speed detection.
Default: 0.0%
Min: 0.0%
Max: 100.0%
L4-02
(49AH)
Speed Agreement Detection Width
Default: 4.0%
Min: 0.0%
Max: 40.0%
L4-03
(49BH)
Speed Agreement Detection Level
(+/-)
L4-03 sets the speed detection level for digital output functions H2- = 13, 14, 15, 16.
L4-04 sets the hysteresis or allowable margin for speed detection.
Default: 0.0%
Min: –100.0%
Max: 100.0%
L4-04
(49CH)
Speed Agreement Detection Width
(+/-)
Default: 4.0%
Min: 0.0%
Max: 40.0%
L4-05
(49DH)
Speed Reference Loss Detection
Selection
0: Stop. Drive stops when the speed reference is lost.
1: Run. Drive runs at a reduced speed when the speed reference is lost.
Default: 0
Min: 0
Max: 1
L4-06
(4C2H)
Speed Reference at Reference Loss Sets the percentage of the speed reference that the drive should run with when the speed
reference is lost.
Default: 80%
Min: 0.0%
Max: 100.0%
L4-07
(470H)
Speed Agree Detection Selection
0: No detection during baseblock
1: Detection always enabled
Default: 0
Min: 0
Max: 1
L4-13
(4F6H)
Door Zone Level
Sets the door zone speed level. The "door zone" multi-function digital output is closed when the
speed falls below this level.
Default: 0.0%
Min: 0.0%
Max: 100.0%
No. (Addr.)
Name
Description
Setting
Page
L5-01
(49EH)
Number of Auto Reset Attempts
Sets the number of times the drive may attempt to reset after the following faults occur: GF, LF,
oC, ov, rr, oH1, oL1, oL2, oL3, oL4, UL3, UL4.
Default: 0
Min: 0
Max: 10
L5-02
(49FH)
Fault Output Operation during
Auto Reset
0: Fault output not active.
1: Fault output active during reset attempt.
Default: 0
Min: 0
Max: 1
L5-06
(522H)
Undervoltage Fault Reset
Selection
0: Same as L5-01 condition
1: Always automatically reset UV1
Default: 0
Min: 0
Max: 1
No. (Addr.)
Name
Description
Setting
Page
L6-01
(4A1H)
Torque Detection Selection 1
0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Default: 0
Min: 0
Max: 8
L6-02
(4A2H)
Torque Detection Level 1
Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
L6-03
(4A3H)
Torque Detection Time 1
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 1.
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_