S5-01: short floor operation selection, S5-02: nominal speed for short floor calculation, S5-03: short floor minimum constant speed time – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 258: 11 s: elevator parameters, Enables and disables the short floor function

5.11 S: Elevator Parameters
258
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
■
S5-01: Short Floor Operation Selection
Enables and disables the Short Floor function.
Note: 1. The Short Floor and Advanced Short Floor functions cannot be used during Rescue Operation.
2. Do not use Short Floor or Advanced Short Floor when the analog input terminals are configured to supply the speed reference.
3. The drive will accelerate or decelerate to the specified speed reference at the specified Accel/Decel rate if the speed priority is set for
multi-step speed reference (d1-18 = 0 or 3) and the leveling speed reference is selected during Short Floor or Advanced Short Floor.
Setting 0: Disabled
Setting 1: Enabled (Short Floor Operation)
Setting 2: Enabled (Advanced Short Floor Operation)
■
S5-02: Nominal Speed for Short Floor Calculation
Determines the rated speed used to calculate the distance for the Short Floor function when speed priority is set for Multi-
step Speed Reference (d1-18 = 0 or 3).
■
S5-03: Short Floor Minimum Constant Speed Time
Sets the minimum time of the constant speed operation when the Advanced Short Floor function is enabled (S5-01 = 2).
Constant speed
operation at
less than the
rated speed
Not Available.
Before start
Operates at the leveling speed.
No.
Parameter Name
Setting Range
Default
S5-01
Short Floor Operation Selection
0 to 2
0
No.
Parameter Name
Setting Range
Default
S5-02
Nominal Speed for Short Floor Calculation
0.0 to 100.0%
0.0%
No.
Parameter Name
Setting Range
Default
S5-03
Short Floor Minimum Constant Speed Time
0 to 2.0 s
0.0 s
Leveling Speed
Input Timing
Short Floor
Advanced Short Floor
(The speed is 40% of the nominal speed or more.)
H1-
= 53
(Leveling Speed)
d1-19
(Nominal Speed)
d1-26
(Leveling Speed)
40% of nominal
speed
ON(close)
0
Operating
speed
Time
(The speed is less than 40% of the nominal speed.)
H1-
= 53
(Leveling Speed)
d1-19
(Nominal Speed)
d1-26
(Leveling Speed)
40% of nominal
speed
ON(close)
0
Operating
speed
Time