B.3 Parameter Table

396

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

o2: Digital Operator Keypad Functions

o3: Copy Function

o1-21

(576H)

Roping Ratio

Sets the roping ratio.
1: 1:1
2: 1:2
3: 1:3
4: 1:4

Default: 2
Min: 1
Max: 4

241

o1-22

(577H)

Mechanical Gear Ratio

Sets the ratio of the gear installed for display unit calculations.

Default:

<2>

Min: 0.10
Max: 100.00

241

o1-23

(174H)

HBB Non Display Select

Shows and hides HBB on the digital operator while the safety signal is being input.
0: Show HBB
1: Hide HBB

Default: 0

Min: 0
Max: 1

242

<1> The control mode determines the selections available. In V/f Control, only settings 1 through 3 are permitted.

<2> Default setting is determined by the control mode (A1-02).

<5> This parameter appears when the drive displays user-set units (o1-03 = 3).

<6> Default setting and setting range changes when inches are selected for the length units (o1-12 = 1). The setting range becomes 3.70 to 78.00

inches, and the default becomes 15.70 inches.

No. (Addr.)

Name

Description

Setting

Page

o2-01

(505H)

<1> Parameter setting value is not reset to the default value when the drive is initialized.

LO/RE Key Function Selection

0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.

Default: 0

Min: 0
Max: 1

242

o2-02

(506H)

STOP Key Function Selection

0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.

Default: 0

Min: 0
Max: 1

242

o2-03

(507H)

User Parameter Default Value

0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.

Default: 0

Min: 0
Max: 2

243

o2-04

(508H)

<1>

Drive Model Selection

Enter the drive model. Setting required only if installing a new control board.

Default: Determined by
drive capacity

Min: –
Max: –

243

o2-05

(509H)

Speed Reference Setting Method
Selection

0: ENTER key must be pressed to enter a speed reference.
1: ENTER key is not required. The speed reference can be adjusted using the up and down
arrow keys only.

Default: 0

Min: 0
Max: 1

243

o2-06

(50AH)

Operation Selection when Digital
Operator is Disconnected

0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.

Default: 0

Min: 0
Max: 1

244

o2-09

(50DH)

Reserved

No. (Addr.)

Name

Description

Setting

Page

o3-01

(515H)

Copy Function Selection

0: Copy select
1: INV

→ OP READ (Read parameters from the drive, saving them onto the digital operator.)

2: OP

→ INV WRITE (Copy parameters from the digital operator, writing them to the drive.)

3: OP

↔ INV VERIFY (Verify parameter settings on the drive to check if they match the data

saved on the operator.)
To read the drive’s parameter settings into the digital operator, set o3-02 to 1 (to allow reading).

Default: 0

Min: 0
Max: 3

244

o3-02

(516H)

Copy Allowed Selection

Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed

Default: 0

Min: 0
Max: 1

244

No. (Addr.)

Name

Description

Setting

Page

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_