D1-19: nominal speed, D1-23: releveling speed, D1-24: inspection operation speed – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 175: D1-25: rescue operation speed, D1-26: leveling speed, 4 d: reference settings, Sets intermediate speeds 1 through 3

5.4 d: Reference Settings
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
175
P
a
ra
me
te
r De
ta
ils
5
■
d1-19: Nominal Speed
Sets the nominal speed when a multi-function input terminal is programmed for “Nominal speed” (H1- = 50).
■
d1-20, d1-21, d1-22: Intermediate Speeds 1 to 3
Sets intermediate speeds 1 through 3.
■
d1-23: Releveling Speed
Sets the releveling speed when a multi-function input terminal is programmed for “Releveling speed” (H1- = 52).
■
d1-24: Inspection Operation Speed
Sets the inspection speed when a multi-function input terminal is programmed for “Inspection speed” (H1- = 54). A
description of the inspection speed can be found in
Inspection Operation on page 124
.
■
d1-25: Rescue Operation Speed
Determines the speed during Rescue Operation.
Refer to Rescue Operation on page 131
for details.
■
d1-26: Leveling Speed
Sets the inspection speed when a multi-function input terminal is programmed for “Leveling speed” (H1- = 53).
No.
Parameter Name
Setting Range
Default
d1-19
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Nominal Speed
0.00 to 100.00%
100.00%
No.
Parameter Name
Setting Range
Default
d1-20
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Intermediate Speed 1
0.00 to 100.00%
0.00%
d1-21
Intermediate Speed 2
0.00 to 100.00%
0.00%
d1-22
Intermediate Speed 3
0.00 to 100.00%
0.00%
No.
Parameter Name
Setting Range
Default
d1-23
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Releveling Speed
0.00 to 100.00%
0.00%
No.
Parameter Name
Setting Range
Default
d1-24
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Inspection Operation Speed
0.00 to 100.00%
50.00%
No.
Parameter Name
Setting Range
Default
d1-25
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Rescue Operation Speed
0.00 to 100.00%
10.00%
No.
Parameter Name
Setting Range
Default
d1-26
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to Defaults and Setting Ranges by Display Unit
for details.
Leveling Speed
0.00 to 100.00%
8.00%