C.4 MEMOBUS/Modbus Setup Parameters
C.4 MEMOBUS/Modbus Setup Parameters
◆ MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
■
H5-01: Drive Slave Address
Sets the drive slave address used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but
no two drives may share the same address.
■
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note: Cycle the power after changing this parameter to enable the new setting.
■
H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
■
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
Setting 0: Ramp to stop (uses the deceleration ramp currently enabled)
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
No.
<1> If the address is set to 0, no response will be provided during communications.
Parameter Name
Setting Range
Default
H5-01
Drive Slave Address
0 to FFH
1FH
No.
Parameter Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 5
3
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
5
38400 bps
1
2400 bps
6
57600 bps
2
4800 bps
7
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
–
–
No.
Parameter Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
No.
Parameter Name
Setting Range
Default
H5-04
Stopping Method after Communication Error
0 to 3
3