Temperature derating, Altitude derating, Temperature derating altitude derating – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 363: Figure a.4, Parameter settings, Yea_ tmonly, A.5 drive derating data

A.5 Drive Derating Data
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
363
Spe
c
if
ic
at
ions
A
Figure A.4
Figure A.4 Carrier Frequency Derating (4A0140 to 4A0260)
◆ Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in
is installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure
reliable drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
■
Parameter Settings
IP00 Enclosure
Drive operation between -10
°C and 50°C allows 100% continuous current without derating.
IP00 Enclosure with Top Protective Cover
Drive operation between -10
°C and 40°C allows 100% continuous current without derating. Operation between 40°C and
50
°C requires output current derating.
Figure A.5
Figure A.5 Ambient Temperature and Installation Method Derating
◆ Altitude Derating
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m both the drive
rated voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m.
No.
Name
Description
Range
Default
L8-12
Ambient Temperature
Setting
Adjust the drive overload (oL2) protection level when the drive is installed in an environment
that exceeds its ambient temperature rating.
-10 to 50
40 °C
L8-35
Installation Method
Selection
0: IP00 Enclosure
2: IP00 Enclosure with Top Protective Cover
0 or 2
Determined by
o2-04
Drive Rated
70
% of Drive Rated
5 kHz
10 kHz
0
4A0140 to 4A0260
YEA_
TMonly
100
85
0
L8-35=2 : NEMA Type 1 Enclosure
L8-35=0 : IP00 Enclosure
-10
40
50
Drive Rating
(%)
L8-12
(Ambient temp : °C)
YEA_
TMonly