B.3 Parameter Table
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
379
Pa
ra
met
er
L
is
t
B
F1-03
(382H)
Operation Selection at Overspeed
(oS)
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
F1-04
(383H)
Operation Selection at Deviation
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 3
Min: 0
Max: 3
F1-05
(384H)
Encoder 1 Rotation Direction
Selection
0: A phase leads B in up direction
1: B phase leads A in up direction
Default:
Min: 0
Max: 1
F1-06
(385H)
PG 1 Pulse Monitor Output
Division Ratio
Sets the division ratio for the pulse monitor used of the PG option card installed to connector
CN5-C. By setting “xyz”, the division ratio becomes = [(1 + x) / yz]. If only using the A pulse
for one track input, then the input ratio will be 1:1, regardless of what F1-06 is set to.
Default: 1
Min: 1
Max: 132
F1-08
(387H)
Overspeed Detection Level
Sets the overspeed detection level as a percentage of the maximum output frequency.
Default: 115%
Min: 0%
Max: 120%
F1-09
(388H)
Overspeed Detection Delay Time
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
F1-10
(389H)
Excessive Speed Deviation
Detection Level
Sets the speed deviation detection level as a percentage of the maximum output frequency.
Default: 10%
Min: 0%
Max: 50%
F1-11
(38AH)
Excessive Speed Deviation
Detection Delay Time
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).
Default: 0.5 s
Min: 0.0 s
Max: 10.0 s
F1-14
(38DH)
PG Open-Circuit Detection Time
Sets the time required to trigger a PG Open fault (PGo).
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
F1-18
(3ADH)
dv3 Detection Selection
0: Disabled
n: Sets the number of dv3 situations that may be detected before triggering an actual dv3 fault.
Default: 10
Min: 0
Max: 10
F1-19
(3AEH)
dv4 Detection Selection
0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.
Default: 128
Min: 0
Max: 5000
F1-20
(3B4H)
PG Option Card Disconnect
Detection 1
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
F1-29
(3BFH)
dEv Detection Condition Selection
Selects when DEV is active.
0: After speed reference, soft starter output and motor speed have matched once.
1: After speed reference and soft starter output have matched once.
2: Always during Run
Default: 2
Min: 0
Max: 2
F1-50
(3D2H)
Encoder Selection
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communication + Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: Hiperface
Default: 0
Min: 0
Max: 2
F1-51
(3D3H)
PGoH Detection Level
Sets the level for detecting PG Hardware Fault (PGoH). Available when F1-20 = 1
Default: 80%
Min: 1%
Max: 100%
F1-52
(3D4H)
Communication Speed of Serial
Encoder Selection
Selects the communication speed between the PG-F3 option and serial encoder.
0: 1M bps/9600 bps
1: 500k bps/19200 bps
2: 1M bps/38400 bps
3: 1M bps/38400 bps
Default: 0
Min: 0
Max: 3
F1-63
(2DFH)
PG-E3 R Track Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
No.(Addr.)
Name
Description
Setting
Page
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV
common
_
CLV
CLV/PM
V/f
OLV