SiteOmat Setup and Maintenance Manual – MDE 4817G

To define a probe as a water/oil separator sensor proceed as follows:

1. Select the Is Separator checkbox in the Probes dialog box (see Figure 7-9)

2. Click on the Setup Separator button. The Probes Oil/Water Separator dialog box appears

(see Figure 7-12)

Figure 7-12. Probes Oil/Water Separator Dialog Box

3. Verify that water is at maximum level and click on the Read button to receive and enter the

initial level (A in Figure 7-13)

4. Define the maximum drop of the sensor from the initial level. In cases where this threshold

is passed and the tank should be filled, the system generates an alarm (B in Figure 7-13)

5. Define the maximum distance between oil and water level sensors. In cases where this

threshold is passed, the system generates an alarm to prevent waste from leaking trough the

tank outlet (C in Figure 7-13)

6. Click Save to apply the changes and close the dialog box

Figure 7-13. Oil/Water Separator Initial and Alarm Levels

7-7.2.3. Finalizing Probes Settings

Once all the parameters have been defined, proceed as follows:

1. Click New or Modify in the Probes dialog box to save all the settings