beautypg.com

Gasboy SiteOmat Maintenance Manual User Manual

Page 139

background image

135

SiteOmat Setup and Maintenance Manual – MDE 4817G

7-5. ORPT

7-5.1. General

To open the OrPT dialog box (see Figure 7-5), select the OrPT tab in the Setup screen.

The OrPT definition has several options. First, it requires a bus and an RS-485 addresses. Then,

additional features can be defined.

To define an OrPT, type its Name, then select its Bus. All OrPT supported in SiteOmat

communicate in Orpak frame, therefore the Bus selection is restricted.

Model

field is not applicable and is disabled.

Next, define its Hex Address in the appropriate box. Refer to Table 2-2.

Figure 7-5. OrPT Dialog Box

7-5.2. Additional Features

To enter the additional features, click on the Addtl. Features button. A dialog box appears (see

Figure 7-6).