Gasboy SiteOmat Maintenance Manual User Manual
Page 144

140
SiteOmat Setup and Maintenance Manual – MDE 4817G
Figure 7-9. Probes Dialog Box
7-7.2.1. Strapping
If Hectronic or Start Italiana probes are used (without an ATG controller), they do not provide
volume (only height), click on the Strapping button (otherwise the button remains disabled) The
Strapping dialog box appears (see Figure 7-10).
This dialog box contains a strapping definition table that allows calculating the volume of product
in a tank according to given depths/levels.
Type the following values in the strapping table:
• Volume
– Expected volume in tank
• Diff
– The difference between two measurement points. Utilized to find out the volume in a
specific point in the range (For example the user defines points at each 10 inches, the formula
uses the diff field in cases where the probe informs height of 35 inch). When building the table,
the user needs to calculate the diff for point B as follows:
(Volume B – Volume A) / (Height B – Height A) /10
• Height
– the actual fuel height measurement in the tank.
Click on the Modify button to record the values in the table.
A strapping table can also be loaded from a CSV file by clicking on the Load button.