Next define the volume Capacity of the tank that the probe is controlling. The volume is set in
Liters/Gallons.
The Water Offset and Fuel Offset fields enable users to initialize the system when utilizing Start
Italiana probes, setting the actual height of water and fuel. For example, if a tank is empty and the
probe reads 3 cm. of water, enter the received reading to the Water Offset text box. The Controller
compensates the value.
The following parameters are required for the auto calibration process:
a. Diameter: Diameter of the tank
b. Min. level for calibration done alarm: Minimum low volume level to be covered
required for auto-calibration completion, set in percentage of tank capacity
c. Max . level for calibration done alarm: Minimum high volume level to be covered
required for auto-calibration completion, set in percentage of tank capacity
NOTE
In addition to coverage parameters, the auto
calibration is completed if the following condition is
met:
Maximum volume difference between two sampling
points should not be higher than the tank capacity
divided by the number of points required for the
specific TLG.
Since the system checks for Auto Calibration completion on a daily base, the alarm is
generated again each day until auto calibration is stopped for this probe (OFF).
d. Camber Radius: Radius of the tank cambers
e. Tank length: Length of the tank from side to side, not including cambers
f. Is divide: Select this checkbox if the tank has 2 compartments