139

SiteOmat Setup and Maintenance Manual – MDE 4817G

Next define the volume Capacity of the tank that the probe is controlling. The volume is set in

Liters/Gallons.

The Water Offset and Fuel Offset fields enable users to initialize the system when utilizing Start

Italiana probes, setting the actual height of water and fuel. For example, if a tank is empty and the

probe reads 3 cm. of water, enter the received reading to the Water Offset text box. The Controller

compensates the value.

The following parameters are required for the auto calibration process:

a. Diameter: Diameter of the tank

b. Min. level for calibration done alarm: Minimum low volume level to be covered

required for auto-calibration completion, set in percentage of tank capacity

c. Max . level for calibration done alarm: Minimum high volume level to be covered

required for auto-calibration completion, set in percentage of tank capacity

NOTE

In addition to coverage parameters, the auto

calibration is completed if the following condition is

met:

Maximum volume difference between two sampling

points should not be higher than the tank capacity

divided by the number of points required for the

specific TLG.

Since the system checks for Auto Calibration completion on a daily base, the alarm is

generated again each day until auto calibration is stopped for this probe (OFF).

d. Camber Radius: Radius of the tank cambers

e. Tank length: Length of the tank from side to side, not including cambers
f. Is divide: Select this checkbox if the tank has 2 compartments