beautypg.com

AMETEK Lx Series II Programming Manual User Manual

Page 184

background image

Programming Manual

Lx \ Ls Series II

180

8.2.13 APE Message Separators

A complete message consists of a header and an argument. Since more than one message can be
sent in a setup string, message separators included in the string between the message will make it
more readable to the human operator. Three message separators are recognized: the comma (,),
semicolon (;) and a space. Since these separators are ignored, they may be dispersed throughout a
setup string.

The following are two examples of ASCII strings with separators:

PHZA90;FRQ60;AMP115

CRL,90;FRQ50;AMP,120

8.2.14 Service Requests

After power-up the GPIB Service Request (SRQ) will be generated after any error (example. syntax,
output fault, etc.) as long as the Ls Unit is in APE mode. This SRQ output can be inhibited by the
SRQ header followed by the single digit "0". The SRQ can be re-enabled by the SRQ header
followed by 1. Sending SRQ2 causes an SRQ to be generated after the execution of a setup string
or when data is available after a measurement query. The setup string can be of any type: ramp,
calibration, etc.

The following example disables the GPIB SRQ.

SRQ0

8.2.15 Serial Poll Status Byte

– Error Messages

Once the bus controller has detected the SRQ, it must determine the instrument needing service by
the Serial Poll. During the polling routine the instrument needing service will return a Status Byte
(STB) greater than decimal 63. The Status Byte values for various faults are given in Table 8-6.

Table 8-6.shows all of the possible error messages that can be generated by the AC Power
System. The equivalent error messages used in SCPI mode will be displayed on the front panel
of the AC Power System.

SRQ 1

SRQ 1

Reported Message

Cause

64

0

AMP A FAULT

Overload or sense line fault

65

1

AMP B FAULT

Overload or sense line fault

66

2

AMP AB FAULT

Overload or sense line fault

67

3

AMP C FAULT

Overload or sense line fault

68

4

AMP AC FAULT

Overload or sense line fault

69

5

AMP BC FAULT

Overload or sense line fault

70

6

AMP ABC FAULT

Overload or sense line fault

71

7

CRL FAULT

Output current exceeds program value

72

8

TEMP A FAULT

Amplifier over temperature

73

9

TEMP B FAULT

Amplifier over temperature

74

10

TEMP AB FAULT

Amplifier over temperature

75

11

TEMP C FAULT

Amplifier over temperature

76

12

TEMP AC FAULT

Amplifier over temperature

77

13

TEMP BC FAULT

Amplifier over temperature

78

14

TEMP ABC FAULT

Amplifier over temperature