beautypg.com

Outstation mode, Fault latch – Wavetronix Click 400 (900 MHz radio) (CLK-400) - User Guide User Manual

Page 92

background image

CHAPTER 9 • CLICK 110

91

Outstation Mode

Also on this switch is the outstation mode. This is configured on the third DIP switch, la-

beled S3, using switch 6 (S3:6).

Note

This parameter can only be changed using the DIP switches.

The Click 110 can be used with two brands of outstations, Peek and Siemens. Because of

differences in the way these two operate, you need to use switch 6 on the S3 DIP switch to

tell the Click 110 with which outstation it is going to be used.

If S3:6 is off (down), the Click 110 is set to work with a Peek brand outstation. If S3:6 is on

(up), the Click 110 is set to work with a Siemens brand outstation.

S3: Outstation Mode

6

State

Off

Peek

On

Siemens

Table 9.5 – DIP Switch Outstation Mode Settings

Note

In Peek mode the Isolated fault output channels are N/C; in Siemens mode they are
N/O. The Master Fault output relay is also opposite when switching between the two
modes. Refer to the pinout table earlier in this chapter for more information.

Because Outstation mode can only be changed using the DIP switches (though it can be

viewed elsewhere), there is no option for selecting Hardware or Software configuration modes.

Fault Latch

The last option that can be configured on the DIP switches is fault latching. This is config-

ured on the third DIP switch, labeled S3, using switch 8 (S3:8).

Note

This parameter can only be changed using the DIP switches.

This manual is related to the following products: