beautypg.com

Power and configuration, Autobaud configuration – Wavetronix Click 400 (900 MHz radio) (CLK-400) - User Guide User Manual

Page 140

background image

CHAPTER 12 • CLICK 172/174 139

Power and Configuration

The Click 172/174 will automatically power up when the cards are inserted into a detector

card rack that is receiving power.

Note

Before configuring the Click 172/174 cards, make sure that SmartSensor Manager is
not running and that no other devices are communicating on the RS-485 bus.

Autobaud Configuration

Follow the steps below to autobaud the Click 172/174 cards with the sensor:
1 After inserting the Click 172/174 card into the detector rack with the Settings switch in

position 3 (Run Setting), connect the jumper cable directly from a Click 200 module to

the RJ-11 port of the card being configured.

2 Move the Settings switch to the 1 (Mode) position. This will establish communication

with the SmartSensor at one of the four supported RS-485 baud rates (9600, 19200,

38400 and 57600 bps), and then query the sensor to set the loop-spacing parameters.

The sensor will automatically be configured to push event or actuation data based on

sensor detections.

Note

If a flashing “Er” appears in the display instead of the mode, then the baud rate was
not properly configured. Open SmartSensor Manager and confirm that the Smart-
Sensor’s RS-485 baud rate is set to 9600, 19200, 38400 or 57600 bps. Close Smart-
Sensor Manager and move the Settings switch to position 3 (Run Setting) to clear
the error. If the Click 172/174 autobaud process continues to fail, it may be neces-
sary to reopen SmartSensor Manager and decrease the sensor’s RS-485 baud rate
setting. Select a lower baud rate, close SmartSensor Manager and repeat the Click
172/174 auto-configuration process.

Click 172/174 Configuration

Click 172/174 configuration allows you to select the card’s operation mode and map chan-

nel outputs to inputs.

This manual is related to the following products: