Click 340/341/342 Ethernet

INSTALLER QUICK-REFERENCE GUIDE

2

Wire power and communication

Unlike many other Click devices, the Click 340, 341 and 342 do not mount over the T-bus, meaning that

power and communications will have to be wired in. Follow the steps below to install and wire a Click 340,

341 or 342:
1 Attach a wire for +DC (red is standard) to the s 1 crew terminal marked US1.

2 Attach a wire for -DC (black is standard) to the screw terminal marked GND.

3 Attach the other end of these two wires to a DC power source. In a traffic installation with other Click

modules, the best way to do this is to attach a female 5-screw terminal block to the end of the T-bus and

wire the +DC and -DC from steps 1 and 2 into the top two terminal connectors.

4 Make sure the DIN rail is properly grounded, as the Click 340–342 are grounded via a foot that con-

nects with the DIN rail.

˽

RJ-45 jacks (all modules) – Connect an Ethernet cable here

˽

SC fiber optic connectors (multimode: Click 341 / single-mode: Click 342) – Attach fiber optic cables by

pushing the connector down until it engages with a click

www.wavetronix.com

801.734.7200

1

Mount the device

The Click 340–342 mount on a DIN rail. To mount the device, simply hook the lip over the lower edge of the

DIN rail, and use a rocking motion to snap the module into place.

Note. Do not mount over the T-bus.