beautypg.com

Wavetronix Click 400 (900 MHz radio) (CLK-400) - User Guide User Manual

Page 105

background image

104

CHAPTER 9 CLICK 110

The System > Settings tab lets you configure and view many of the parameters that are also

available elsewhere on the device (see Table 9.1 earlier in this chapter for more informa-

tion). The tab has the following parameters (see Figure 9.11 and Table 9.16):

Figure 9.11 – Expert Driver Settings Tab

Note

These parameters can also be configured using the DIP switches or the front panel
menu; if in the DIP switches they are set to Hardware mode, the parameters will ap-
pear grayed out on this screen.

Setting

Description

Baud Rate for Bus 1

Lets you change the baud rate, in bps, of bus 1.

Baud Rate for Bus 2

Lets you change the baud rate, in bps, of bus 2.

Input Mapping

Lets you assign input datagram channels received from the sensor to
the device’s four output channels. The outputs are mapped sequen-
tially—that is, they can only be mapped in numerically ordered groups
of four (1–4, 5–8, etc.). See Input Mapping in either the DIP Switches
or Front Panel Menu sections in this chapter for more information.

Channel Enable

Lets you choose which of the output channels are enabled. Any com-
bination of outputs can be enabled. A disabled output will never enter
the detection state, and will never indicate a fault condition.

Fault Latch

Lets you view if Fault Latch is enabled. See Fault Latch in the DIP
Switches section of this chapter for more information.

Fault latching can only be configured using the DIP switches, so this
parameter will always be grayed out, allowing you to view but not
change the configuration of this parameter.

This manual is related to the following products: