Tank, Pump, and PCU File Setup - Keypad

About the PCU File

Page 54 MDE-4338A TopKAT™ Fuel Management System Operation Manual · February 2009

Configure Master Unit for Electronic Pump

To configure Master Unit for Electronic Pump, proceed as follows:

1

At PCU SETUP: LOAD # SATELLITES, press ENTER.

2

Type the number of satellite units (1 - 7) and press ENTER. Use the down arrow to proceed.

3

At EDIT PCUS, press ENTER.

4

At EDIT PCUS: MASTER, press ENTER. Define the characteristics of your master unit.

• At LOAD # of PUMPS, press ENTER. Type the number of pumps attached to the master

(1 - 8) and press ENTER. Use the down arrow key to proceed.

• At LOAD BASE PUMP, press ENTER. Indicate the base pump number (01 - 99) and

press ENTER. Use the down arrow to proceed.

• At PCU ASSIGNMENTS, press ENTER. The system displays the current slots assigned

to each pump starting with the lowest pump number. Use the down arrow to display other
pumps.

• At PUMP #nn SLOT, press ENTER. The prompt PCU SLOT appears. Type the required

slot number and press ENTER.

• Press PREV until EDIT PCUS: MASTER displays.

5

Press the down arrow until EDIT PCUS: SATELLITES displays. Press ENTER. Continue
with the procedure

“Configure Satellite PCUs for Mechanical I/F Pumps”

on

page 54

.

Configure Satellite PCUs for Mechanical I/F Pumps

At EDIT SATELLITE PCU: SATELLITE #1, press ENTER to display the characteristics for
the first satellite. If another satellite is required, press the arrow keys until the required number
displays. Then press ENTER.

• At LOAD # of PUMPS, press ENTER. Type the number of pumps attached to the satellite

(1 or 2) and press ENTER. Use the down arrow key to proceed.

• At LOAD BASE PUMP, press ENTER. Indicate the base pump number (01 - 99) and

press ENTER. Use the down arrow to proceed.

• At MECH PUMP SETUP, press ENTER. The system displays the current pump numbers.

Press ENTER at the required pump number. Use the down arrow to proceed.

• At PULSE RATE, press ENTER. Use the down arrow until the required pulse rate

displays and press ENTER. Use the down arrow to proceed.

• At PUMP SWITCH TIMER, press ENTER. Type a value from .1 to 1.0 and press

ENTER (refer to

“Mechanical Interface Option”

on

page 20

for details on this parameter).

• Press PREV until EDIT SATELLITE PCU: SATELLITE #x displays. If configured for