Load password (l pa), Load pump (l pu), Load range (l ra) – Gasboy TopKAT Operation Manual User Manual
Page 111

MDE-4338A TopKAT™ Fuel Management System Operation Manual · February 2009
Page 103
Accessing the Terminal Commands
Terminal Commands
Load PAssword (L PA)
Use this command to set a password for accessing the terminal command set. While the
keypad manager password is limited to four digits; the manager password for the terminal can
be 1 to 10-alphanumeric characters. The terminal password is factory-set to GASBOY.
1
Type L PA.
The system responds LOAD PASSWORD:
2
Type the password (characters typed are not displayed).
~ OR ~
If you do not wish to change the password, press ENTER to retain the existing password.
Load PUmp (L PU)
Use this command to define the characteristics of your pump.
1
Type L PU.
The system responds LOAD PUMP TABLE ENTER PUMP #:
2
Type the pump number (01 - 99) and press ENTER.
The system responds ENTER TANK ASSIGNMENT: (x).
3
Enter the one-digit number for the tank containing the product.
The system responds ENTER TOTALIZER: (xxxxxxx.xxx).
4
Enter up to 10 digits for the totalizer value from the pump, if required.
The system responds ENTER TOTALIZER RESET DATE (mmddyy): (xxxxxx).
5
Enter the current date (if setting the totalizer).
The system responds ENTER PULSE RATE.
6
Enter the pulse rate required.
The system responds ENTER PUMP SWITCH TIME.
7
Enter a value between 0.1 and 1.0.
The system displays the ENTER PUMP # prompt.
8
until all pumps are defined.
Load RAnge (L RA)
Use this command to load a four-digit value for the maximum number of miles that may be
traveled between fuelings for an odometer to be considered reasonable.
1
Type L RA.
The system responds LOAD REAS RANGE (xxxx):
2
Type a four-digit value.