Tank, Pump, and PCU File Setup - Keypad
About the Pump File
Page 50 MDE-4338A TopKAT™ Fuel Management System Operation Manual · February 2009
Load # of Pumps (Standalone TopKAT, Master Electronic, Master
Mechanical PCU)
Use this to load the number of pumps in your configuration (1 through 8).
1
Access the Pump File. At LOAD # OF PUMPS, press ENTER.
2
Type the number (1 through 8) and press ENTER. Use the down arrow key to proceed.
Load Base Pump (Standalone TopKAT and Master Electronic, Master
Mechanical PCU)
Use LOAD BASE PUMP to enter a starting pump number (from 1 - 99) depending on how
you wish your pumps to be numbered.
1
Access the Pump File. Press the arrow keys until LOAD BASE PUMP appears. Press
ENTER.
2
Indicate the base pump number (01 - 99) and press ENTER. Use the down arrow to proceed.
Load Pump Table
Use LOAD PUMP TABLE to load specific information about a pump.
1
Access the Pump File. Press the arrow keys until LOAD PUMP TABLE appears. Press
ENTER. If your TopKAT is standalone, the system displays PUMP #xx, TK:x,EN. If you
have the master/satellite option, the prompt displays the pump numbers in numeric pump
(master/satellite) pairs: PUMP #xx(y), TK:x,EN. (y) is set to M (master) for electronic or
mechanical PCU options. If you use the mechanical I/F option or have combination electronic
and mechanical, (y) is set to M or the satellite number.
Consider the following example:
PUMP #01(1), TK:1,ENPump 1(satellite 1), tank 1, enabled.
PUMP #02(M), TK:1,ENPump 2(master), tank 1, enabled.
PUMP #03(2), TK:2,ENPump 3(satellite 2), tank 2, enabled.
PUMP #04(2), TK:2,ENPump 4(satellite 2), tank 2, enabled.
2
Use the arrow key to display the required pump and press ENTER.
3
At TANK ASSIGNMENT, press ENTER. Type the tank number assigned to the pump. Tank
numbers can be 1 - 9. Press ENTER. Use the down arrow key to proceed.
4
At TOTALIZER, press ENTER, then enter the totalizer reading from the pump. Enter up to
10 digits (xxxxxxx.xxx). The decimal point is fixed, so enter the appropriate number of zeros
to form the correct number. Press ENTER. This number is incremented as fueling transactions
occur. Use the down arrow key to proceed.
5
At TOTALIZER RESET DATE, press ENTER. The system displays TOT RESET:
MMDDYY. Type the date the totalizer is reset and press ENTER. Use the down arrow key to
proceed. Skip to step
unless you have a standalone TopKAT with mechanical pumps.