MDE-4338A TopKAT™ Fuel Management System Operation Manual · February 2009
Page 97
Accessing the Terminal Commands
Terminal Commands
COnfigure SYstem (CO SY) - Master/Satellite Electronic or Mechanical PCU
Use this command to configure the operating characteristics of your master/satellite system.
1
Type CO SY.
The system displays a menu containing the system parameters.
CONFIGURE SYSTEM
1. SITE NO.
2. SYSTEM ID
3. NO. OF PUMPS
4. BASE PUMP NO.
5. PUMP TIMEOUTS
6. NO. OF TANKS
7. POLL ADDRESS
8. NO. OF PCUS
9. NO. OF SATELLITES
10. ALL
ENTER (1-10):
The next system prompt varies depending on the option you select.
• If you select option 10 (All), system parameters display one after the other until all are
completed.
• Refer to the following table for guidance on what to enter for the other prompts.
Descriptions of these parameters appear in
.
Selection
Prompt
Enter
1
LOAD SITE NO: (xxxx)
4-digit site number
2
LOAD SYSTEM ID (xxxx)
4-digit system ID, assigned at the factory
3
LOAD NO. OF PUMPS (x)
number of pumps supported by TopKAT
4
LOAD BASE PUMP NO. (xx)
base pump number (01-99)
5
LOAD PUMP TIMEOUTS (xxx)
time-out value
6
LOAD NO. OF TANKS (x)
number of tanks supported by TopKAT
7
LOAD POLL ADDRESS (xx)
poll address for computer communication (usually 01)
8
LOAD NO. OF PCUS (x)
number of PCUs supported by TopKAT (8 maximum)
9
LOAD NO. OF SATELLITES
number of satellites supported by TopKAT
2
After a selection is complete, the menu reappears. Press ENTER to exit.