System Overview

Communications

Page 14 MDE-4338A TopKAT™ Fuel Management System Operation Manual · February 2009

JP3 and JP4 set the delay time used by leak detectors in submersible pump applications. The
delay time is the period between activation of the submersible pump and activation of the slow
flow valve. Set this time according to the type of leak detector installed on the submersible
pump to allow a normal leak test for each transaction. The delay time should be set to 0
seconds for suction pumps.

JP7 should be open for normal operation. When closed, this switch enables the reset of
electronic totalizers.

JP8 is available only with 9800 software, version 5.3 or higher. Switch 1-8 is set to Closed to
disable RS485 pump stop detection. This is necessary because the TopKAT operates in a half-
duplex configuration and it is possible for the 98xx to detect a false break character when the
half duplex lines switch from receive mode to transmit mode and vice-versa. These random
false break characters will cause the 98xx to terminate the transaction.

SW2-1 through SW2-4
(Only on M06333KXXXX CPU)

Function

Setting

Address 1

All Closed

SW2-5 and SW2-6 - Unit of Measure Selection
(Only on M06333KXXXX CPU)
These two switches set the unit of measure (US gallons, liters, or Imperial gallons) that the
pump/dispenser will be using to meter fuel.

Unit of Measure

SW2-5

SW2-6

US Gallons

Closed

Closed

Liters

Open

Closed

Imperial Gallons

Closed

Open

NOT USED (default US Gallons)

Open

Open

SW2-7 - Electro-mechanical Totalizer Enable
(Only on M06333KXXXX CPU)
This switch is only used on K model dispensers/pumps (excluding the 9850K model). When
closed (“On”), it enables the pump/dispenser to drive electro-mechanical totalizers used on
some K pump models. On A and Q models, this switch is ignored.

EM Totalizer

SW2-7

Enabled

Closed

Disabled

Open

SW1-8

JP8

RS-485 Pump Stop Detection
Disabled

Closed

N/A

JP9

Not used

N/A

Switch SW1/Jumper

Function

Setting

Old CPU

New CPU
(M06333KXXXX)