Component Definition and Maintenance 4-141

7000 ―C‖ Frame - Marine

7000L-UM302B-EN-P – June 2013


-

The last step is to stop the communication between your laptop
and the drive and close the file Example.txt. At your laptop, click
on Transfer menu and select Stop option under Capture Text …
as shown in the screenshot below.

Now close the HyperTerminal program and disconnect the laptop
from the drive.


Overview

In PF7000 drives with ForGe control, a specific memory location has
been set aside to capture and store critical data in the event of a fault
condition. This data is referred to as "Control Data". There are total 8
buffers where the data is stored sequentially on first-in first-out basis,
which ensures the data of 8 most recent faults is always available.
The data can be retrieved for analysis.

The method of retrieving Control Data is explained below.

Required

-

Laptop with Windows HyperTerminal program

-

A null-modem cable with a 9-pin female connector for the laptop
serial port, and a 9-pin male connector for Drive Processor
Module (DPM) data port (J4).

(A serial cable with pins 2-3

swapped at one end will also work)

Printing (Uploading)

Control Data