beautypg.com

Current transformer replacement – Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual

Page 193

background image

Component Definition and Maintenance 4-17

7000 ―C‖ Frame - Marine

7000L-UM302B-EN-P – June 2013

1. Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main power
has been disconnected before working on the
current transformer. Verify that all circuits are
voltage free using a hot stick or appropriate
voltage-measuring device. Failure to do so may
result in injury or death.

2. Note the location of all wires and the orientation of the CT. For

quick reference when checking the orientation of the CT, look for the
white dot.

I M P O R T A N T

I M P O R T A N T

The CT and wires must be in the proper orientation.
Note the position before disassembly.

3. Disconnect the wires.

4. The bus bar must be disassembled to allow removal of the CT.

Remove the M10 hardware to allow the bus bar to slide out.

5. Remove the four screws located in the base of the CT and remove.

6. Replace the CT, ensuring the proper orientation. Fasten the CT

securely with the four screws in the base

7. Reconnect the ring lugs.

8. Replace the bus bar and tighten into place.

Customer Line Terminals

Current Transformers

Figure 4.13 – Line Terminals


Note: Customer terminals shown for bottom cable entry. Terminals
can be removed and re-installed with orientation for top cable entry.

Current Transformer

Replacement