Component Definition and Maintenance 4-99

7000 ―C‖ Frame - Marine

7000L-UM302B-EN-P – June 2013

Isolated Process Receiver

These inputs are individually configurable to accept either a
-10/0/+10V input signal or a 4-20 mA signal. When configured for
voltage input, each channel has an input impedance of 75 Kohms.
When used as a current loop input, the transmitter must have a
minimum loop compliance of 2 volts to satisfy the 100 ohm input
impedance. Regardless of input configuration, each input is
individually isolated to ± 100V DC or 70V RMS AC.

A block diagram of the receiver is shown below.

4,8,12

3,7,11

∩/#

X1

U1

FPGA

DSP

1

st

I/P pins

3

rd

I/P pins

2

nd

I/P pins

A/D

Buffer

1,5,9

2,6,10

Isolation Amplifier

+

+

-

-

Figure 4.72 – Process Loop Receiver Block Diagram