beautypg.com

Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual

Page 16

background image

1-2

Overview of Drive

7000L-UM302B-EN-P – June 2013

7000 “C” Frame - Marine

The Main Benefits of the 7000L “C” Frame Liquid-cooled Drive

Include:

 Completely integrated MV drive package reduces customer

installation costs and start-up time.

 Higher power rating capability (up to 9000 hp / 6715 kW)
 18 Pulse and AFE rectifiers for low harmonic solutions that meet

IEEE 519-1992 Harmonic Guidelines

 Motor friendly current and voltage output waveforms for use

with standard new and existing motors
Inverter duty motors not required
Motor temperature derating not required
No additional dv/dt or peak voltage stress to motor insulation

system

Tested up to 15 kilometers (9.3 miles) cable distance

between drive and motor

 Spacious cable termination cabinet for ease of use by installation

contractor

 Cable termination stabs accommodate:

3 cables in / 3 cables out (Direct-to-Drive or AFE rectifier)
9 cables in / 3 cables out (18 pulse)

Top or bottom entry and exit of line and load cables

 90% of drive losses are rejected outside the control room
 Integral liquid-cooled DC link inductor reduces overall

dimension and eliminates external interwiring.

 Integral pumping panel includes:

Line supply c/w disconnect and fusing
Closed loop coolant system
Iron and chloride free liquid ethyl-glycol / deionized water

mixture

Low conductivity coolant (1-2 micro-Siemens / cm

3

)

Isolated from medium voltage
Fully serviceable low voltage compartment isolated from

medium voltage power

Monitors coolant temperature, flow, level, conductivity, and

pressure

Redundant pumping system (optional)
Automatic pump change over on pump failure
1/2 turn valves with quick disconnect couplers for pump

replacement when drive is operating

Full drip tray to contain any spilled coolant
Drain and fill pump for convenient filling
Industrial schedule 80 CPVC piping for pump panel, headers

and manifolds (no condensation possibility)

Control hardware for cycling of main / redundant cooling

pumps and heat exchanger fans