Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual
Page 277

Component Definition and Maintenance 4-101
7000 ―C‖ Frame - Marine
7000L-UM302B-EN-P – June 2013
ACB Analog Control Board Replacement
To replace the ACB Analog Control Boards:
1. Ensure that all medium voltage and control voltage power to the
drive is isolated and locked out.
2. It is required to remove the transparent sheet on top of the Drive
Processor Module and the Drive Processor Module also before
removing the ACB. Remove the transparent sheet on top of the
DPM by removing the 4 screws.
3. Use static strap before removing any connectors.
4. Remove the connectors J4, J11 and J12 on DPM after proper
identification and marking if necessary. Use the electrical
drawing as the reference. Remove the 4 screws holding it on the
standoffs above the ACB.
5. Gently remove the DPM mounted on the four, 34-pin
connectors.
6. Remove the screws holding encoder interface board and gently
remove the board mounted on the 8 pin connector
7. Remove the connectors J1, J2, J3, J4, J5, J6, J7,J8, J9, J10, J12,
J13, J14, J16, J22, J24, J25, J26, J27 on ACB after proper
identification and marking if necessary. Use the electrical
drawing as the reference.
8. Remove the ACB board by removing the 4 screws, and 6
standoffs screwed to support the DPM & encoder interface
board.
9. Follow Steps 8 – 2 in reverse to reinstall the boards back into
the low voltage control cabinet.
10. Apply Low Voltage power and complete a System Test and
Medium Voltage tests to ensure the new board functions properly.