Specifications (cont.) – Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual
Page 24

1-10
Overview of Drive
7000L-UM302B-EN-P – June 2013
7000 “C” Frame - Marine
Description
Specifications
Number of Rectifier Devices
per phase
Voltage
18-Pulse
AFE / D2D
2400 V
3300 V
4160 V
6600 V
6
6
6
6
2
4
4
6
SCR PIV Rating
(Peak Inverse Voltage)
Voltage
18-Pulse
AFE / D2D
2400 V
3300 V
4160 V
6600 V
4500 V
4500 V
4500 V
6500 V
6500 V
6500 V
6500 V
6500 V
Output Waveform to Motor
Sinusoidal Current / Voltage
Medium Voltage Isolation
Fiber Optic
Modulation Techniques
SHE (Selective Harmonic Elimination)
Synchronous Trapezoidal PWM
Asynchronous and Synchronous SVM
(Space Vector Modulation)
Control Method
Digital Sensorless Direct Vector
Full Vector Control with Tach Feedback (Optional)
Tuning Method
Auto Tuning via Setup Wizard
Speed Regulator Bandwidth
5-25 Radians / Second
Torque Regulator Bandwidth
15-50 Radians / Second
Speed Regulation
0.1% without Tachometer Feedback
0.01-0.02% with Tachometer Feedback
Acceleration/Deceleration Range
Independent Accel/Decel – 4 x 1200 sec.
Acceleration/Deceleration Ramp Rates
4 x Independent Accel/Decel
S Ramp Rate
Independent Accel/Decel – 2 x 1200 sec.
Critical Speed Avoidance
3 x Independent with Adjustable Bandwidth
Stall Protection
Delay / Speed
Load Loss Detection
Adjustable level, delay, speed set points
Control Mode
Speed or Torque
Current Limit
Adjustable in Motoring and Regenerative
Output Frequency Range
0.2-85 Hz
Service Duty Rating
Overload Rating
Normal Duty
Heavy Duty
110% Overload for
1 minute every 10 minutes
(Variable Torque Load)
150% Overload for
1 minute every 10 minutes
(Constant or Variable
Torque Load)
Typical VFD Efficiency
> 98% ( 18 Pulse)
> 97.5% (AFE)
Contact Factory for Guaranteed Efficiency
of Specific Drive Rating
Input Power Factor
AFE Rectifier
0.98 minimum, 30 – 100% Load
IEEE 519 Harmonic Guidelines
IEEE 519 – 1992 Compliant
VFD Noise Level
< 85 dB(A) per OSHA standard 3074
Regenerative Braking Capability
Inherent – No Additional Hardware or Software Required
Flying Start Capability
Yes – Able to Start into and Control a Spinning Load in
Forward or Reverse Direction
Operator Interface
40-character, 16-line formatted text
Languages
English
German
French
Chinese (Mandarin)
Spanish
Portuguese
Italian
Specifications (cont.)