Component Definition and Maintenance

7000L-UM302B-EN-P – June 2013

7000 ―C‖ Frame - Marine

9. Repeat above steps until you have assigned the desired

parameters to all the traces from Trace1 to Trace16.


10. Now press F9 [TRIGGER] key. The first letter in the second line

on the screen will toggle between C and S. The letter C stands
for Continuous and S stands for Single shot. Select S for single
shot.


11. Press F2 [CONDITION] key. The cursor will move to the ―=‖

equal sign. This defines the trigger condition. Press up or down
arrow keys to select + sign as the trigger condition for our
example.

12. Press F3 [DATA] key. The cursor moves to the data field. In our

example we will enter 8 and then press Enter key.

13. Press F4 [RATE] key. The cursor moves to the rate field. Here

we will enter 0, which is the fastest sample rate (1 msec/sample)
and then press Enter key.

Setting up Diagnostic

Trending (cont.)