Wire the 1756-if16 module – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual
Page 70

70
Publication 1756-UM0009C-EN-P - December 2010
Chapter 4 Non-isolated Analog Voltage/Current Input Modules (1756-IF16, 1756-IF8)
Wire the 1756-IF16 Module
Current and voltage wiring examples for the 1756-IF16 module are shown on
the following pages.
1756-IF16 Differential Current Wiring Example.
+
-
+
-
40912-M
1
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
35
36
IN-0
IN-10
IN-1
IN-9
IN-2
IN-8
IN-5
IN-3
IN-6
RTN
IN-7
IN-4
IN-13
IN-12
IN-14
IN-11
RTN
i RTN-0
i RTN-7
i RTN-4
i RTN-6
i RTN-8
i RTN-9
i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13
RTN
i RTN-5
i RTN-1
i RTN-2
i RTN-3
IN-15
i RTN-14
i RTN-15
Shield Ground
Channel 0
Channel 3
Jumper Wires
i
i
A
NOTES:
1. Use the table when wiring your module in differential mode
2. All terminals marked RTN are connected internally.
3. A 249
Ω
current loop resistor is located between IN-x and i RTN-x terminals.
4. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to
maintain the module’s accuracy.
5. Place additional loop devices (strip chart recorders, so forth) at the A location in the current loop.
6. Do not connect more than two wires to any single terminal.
IMPORTANT: When operating in four channel, high-speed mode, only use channels 0, 2, 4 and 6.
Channel
Terminals
Channel
Terminals
Channel 0
IN-0 (+), IN-1 (-) & i RTN-0
Channel 4
IN-8 (+), IN-9 (-) & i RTN-8
Channel 1
IN-2 (+), IN-3 (-) & i RTN-2
Channel 5
IN-10 (+), IN-11 (-) & i RTN-10
Channel 2
IN-4 (+), IN-5 (-) & i RTN-4
Channel 6
IN-12 (+), IN-13 (-) & i RTN-12
Channel 3
IN-6 (+), IN-7 (-) & i RTN-6
Channel 7
IN-14 (+), IN-15 (-) & i RTN-14
2-Wire
Transmitter
A
+
–
4-Wire
Transmitter
Shield Ground
Channel 6
i
A
2
34
User-provided
Loop Power
Device
Supply