beautypg.com

Module resolution (-12…30 mv range) – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 374

background image

374

Publication 1756-UM009C-EN-P - December 2010

Appendix E Additional Specification Information

Module Resolution (-12…30 mV Range)

The table lists the resolution of ControlLogix thermocouple modules when
used in the -12…30 mV input range.

The information represented in the table is shown graphically in the following
illustrations.

Application
Temperature

Module Resolution (in degrees) When Connected to This Thermocouple Type

B

R

S

E

(1)

J

(2)

K

(3)

N

(4)

T

-200 °C (-328 °F)

0.028

0.032

0.046

0.071

0.044

0 °C (32 °F)

0.13

0.13

0.012

0.014

0.018

0.027

0.018

200 °C (392 °F)

0.08

0.08

0.009

0.013

0.018

0.021

0.013

400 °C (752 °F)

0.17

0.07

0.07

0.009

0.013

0.017

0.019

0.011

600 °C (1112 °F)

0.12

0.06

0.07

0.016

0.02

800 °C (1472 °F)

0.09

0.06

0.06

0.02

1000 °C (1832 °F)

0.08

0.05

0.06

1200 °C (2192 °F)

0.07

0.05

0.06

1400 °C (2552 °F)

0.06

0.05

0.06

1600 °C (2919 °F)

0.06

0.05

0.06

1800 °C (3272 °F)

0.06

0.06

0.07

(1)

Type E thermocouples can only be used in applications up to 400 °C (752 °F).

(2)

Type J thermocouples can only be used in applications up to 550 °C (1022 °F).

(3)

Type K thermocouples can only be used in applications up to 700 °C (1292 °F).

(4)

Type N thermocouples can only be used in applications up to 800 °C (1472 °F).

Application Temperature in °C

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.20

-200

0

200

400

600

800

1000

1200

1400

1600

1800

Minimum Amount of
Degree Change Required
for Thermocouple Module
to Report the Change

Thermocouple Module Resolution - Type B Thermocouple Connection in a -12…30 mV Input Range