Appendix A Analog I/O Module Specifications
Environmental Specifications - 1756-IT6I
Attribute
1756-IT6I
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air
60 °C (140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11: Group 1, Class A
ESD Immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV at 5 kHz on shielded signal ports
Surge Transient Immunity
IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF Immunity
IEC 61000-4-6
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports