beautypg.com

Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 286

background image

286

Publication 1756-UM009C-EN-P - December 2010

Appendix A Analog I/O Module Specifications

Current draw @ 5.1V

250 mA

Current draw @ 24V

100 mA

Power dissipation, max

Voltage: 3.7 W
Current: 4.3 W

Thermal dissipation

Voltage: 12.62 BTU/hr
Current: 14.32 BTU/hr

Input impedance

Voltage: > 10 M

Ω

Current: 249

Ω

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

Voltage: 120V AC/DC
Current: 8V AC/DC (with on-board current resistor)

Normal mode noise rejection

60 dB @ 60 Hz

(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)

(1)

Settling time

<80 ms to 5% of full scale

(1)

Calibrated accuracy 25 °C

Better than 0.1% of range

Calibration interval

6 months

Offset drift

2

μ

V/°C

Gain drift with temperature

Voltage: 35 ppm/°C, 80 ppm/°C max
Current: 45 ppm/°C, 90 ppm/°C max

Module error

0.54% of range

Module input scan time, min

25 ms min – floating point
10 ms min – integer

(1)

Isolation voltage

250V (continuous), basic insulation type, input
channels-to-backplane, and input channel-to-channel

Routine tested at 1350V AC for 2 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

1

Wire size

0.33… 2.1 mm

2

(22…14 AWG) solid or stranded copper

wire rated at 90 °C (194 °F ), or greater, 1.2 mm
(0.047 in.) insulation max

(2)

Wire category

2

(3)

North American temperature code

T4A

IEC temperature code

T4

Enclosure type

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, catalog number 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system-level

installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Technical Specifications - 1756-IF6I

Attribute

1756-IF6I