beautypg.com

Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 261

background image

Publication 1756-UM009C-EN-P - December 2010

261

Calibrate the ControlLogix Analog I/O Modules Chapter 11

If your module is not in Program mode, a warning message appears.
You must manually change the module to Program mode before
clicking Yes.

7.

Set the channels to be calibrated.

8.

Click Next.

TIP

You can select whether to calibrate channels in groups all
at once or each channel at a time.

We recommend you calibrate all channels on your module
each time you calibrate. This will help you maintain
consistent calibration readings and improve module
accuracy.