Temperature-measuring Analog Modules (1756-IR6I, 1756-IT6I, and 1756-IT6I2) Chapter 6

Field-side Circuit Diagrams

The diagrams show field-side circuitry for the 1756-IR6I, 1756-IT6I, and
1756-IT6I2 modules.

1756-IR6I Input Circuit

1756-IT6I and 1756-IT6I2 Input Circuit

43497

lexc

Rwire (A)

A/D converter

Vref

Gain = 1

IN-0/A

RTN-0/C

V_RTD + 2 (Vwire)

3-Wire RTD

Gain = 2

Rwire (C)

IN-0/B

lexc

Vwire = lexc x Rwire

V_RTD + 2 (Vwire) - 2Vwire = V_RTD

594

μ

A Excitation

Current (All Ranges)

Rwire for cable B has no effect
because B is a Sense wire with
zero excitation current.

43498

IN-0/A

RTN-0/C

+0.44 V

0.22

μ

F

383

A/D converter

Vref

0.002

μ

F

Gain = 30

20 M

Ω

25 K

5 K

-12 to 78mV

+2.5V

1.96 K