Chapter 2

Analog I/O Operation in the ControlLogix System

If the RTS value is greater than the RPI, the module produces at both the RTS
rate and the RPI rate. Their respective values will dictate how often the
owner-controller will receive data and how many multicasts from the module
contain updated channel data.

In the example below, the RTS value is 100 ms and the RPI value is 25 ms.
Only every fourth multicast from the module will contain updated channel
data.

Triggering Event Tasks

When configured, ControlLogix analog input modules can trigger an event
task. The event task lets you execute a section of logic immediately when an
event (that is, receipt of new data) occurs.

Your ControlLogix analog I/O module can trigger event tasks every RTS, after
the module has sampled and multicast its data. Events tasks are useful for
synchronizing process variable (PV) samples and proportional integral
derivative (PID) calculations.

RTS

100 ms - Updated data

RPI

25 ms - Same input data
as the previous RTS

25

50

75

100 125 150 175

200 225 250 275

300 325 350 375

400

Time (ms)

40946

IMPORTANT

ControlLogix analog I/O modules can trigger event tasks at
every RTS but not at the RPI. For example, in the illustration
above, an event task can be only triggered every 100 ms.