Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual
Page 322

322
Publication 1756-UM009C-EN-P - December 2010
Appendix A Analog I/O Module Specifications
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80... 2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV at 5 kHz on shielded signal ports
Surge Transient Immunity
IEC 61000-4-5
±2 kV line-earth (CM) on shielded signal ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Environmental Specifications - 1756-OF6VI
Attribute
1756-OF6VI
Certifications - 1756-OF6VI
Certification
(1)
1756-OF6VI
UL
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.
CE
European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
• EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV
TÜV Certified for Functional Safety:
Capable of SIL 2
(1)
When marked. See the Product Certification link a
for Declarations of Conformity, Certificates, and other certification details.