ControlLogix Analog I/O Module Features Chapter 3

The table lists the resolution for each module’s range.

Current Values Represented in Engineering Units

Module

Range

Number of
significant bits

Resolution

1756-IF16 and
1756-IF8

+/- 10.25V

0…10.25V

0…5.125V

0…20.5 mA

16 bits

320 µV/count

160 µV/count

80 µV/count

0.32 µA/count

1756-IF6CIS

0 mA…21 mA

16 bits

0.34 µA/count

1756-IF6I

+/- 10.5V

0…10.5V

0…5.25V

0…21 mA

16 bits

343 µV/count

171 µV/count

86 µV/count

0.34 µA/count

1756-IR6I

1…487

Ω

2…1000

Ω

4…2000

Ω

8…4020

Ω

16 bits

7.7 M

Ω

/count

15 M

Ω

/count

30 M

Ω

/count

60 M

Ω

/count

1756-IT6I and
1756-IT6I2

-12…30 mV

-12…78 mV

16 bits

0.7 µV/count

1.4 µV/count

1756-OF4 and
1756-OF8

+/- 10.4V

0…21 mA

16 bits

15 bits

320 µV/count

0.65 µA/count

1756-OF6VI

+/- 10.5V

14 bits

1.3 mV

1756-OF6CI

0…21 mA

13 bits

2.7 µA

IMPORTANT

Because these modules must allow for possible calibration
inaccuracies, resolution values represent the available
Analog to Digital or Digital to Analog counts over the
specified range.