beautypg.com

Calibrate your input modules, Calibrating in either program or run mode, Calibrating the 1756-if16 or 1756-if8 modules – Rockwell Automation 1756-XXXX ControlLogix Analog I/O Modules User Manual

Page 235

background image

Publication 1756-UM009C-EN-P - December 2010

235

Calibrate the ControlLogix Analog I/O Modules Chapter 11

Calibrating in Either Program or Run Mode

You must be online to calibrate your analog I/O modules by using
RSLogix 5000 software. When you are online, you can choose either Program
or Run mode as the state of your program during calibration.

We recommend that your module be in Program mode and not be actively
controlling a process when you calibrate it.

Calibrate Your Input
Modules

Input calibration is a multi-step process that involves multiple services being
sent to the module. This section has four parts as shown in the table. Each
input module requires attention be paid to specific calibration ranges.

Calibrating the 1756-IF16 or 1756-IF8 Modules

The 1756-IF16 or 1756-IF8 modules are used in applications requiring voltage
or current. The modules offer four input ranges:

• -10…10V

• 0…5V

• 0…10V

• 0…20 mA

However, you can only calibrate these modules using a voltage signal.

IMPORTANT

The module freezes the state of each channel and does not
update the controller with new data until after the calibration
ends. This could be hazardous if active control were attempted
during calibration.

Topic

Page

Calibrating the 1756-IF16 or 1756-IF8 Modules

235

Calibrating the 1756-IF6CIS or 1756-IF6I Modules

241

Calibrating the 1756-IR6I

248

Calibrating the 1756-IT6I or 1756-IT6I2

253

IMPORTANT

Regardless of what application range is selected prior to
calibration, all calibration uses a +/-10V range.